Lavspenning/Kabler/LV installasjonskabler
1 SCOPE
1.1 Purpose
The purpose of the technical specification is to provide guidance for the production, test procedures and delivery of products according to stated requirements. The technical specification contains technical and functional requirements to be fulfilled.
The cables shall provide capability to transfer power. The cables shall be free of halogens and self-extinguishing. The cables are used for general purpose power applications.
Explanation to the four letter code (IFSI) included in the designation:
I (1. letter) = massive insulation of halogen-free polymer (self-extinguishing)
F (2. letter) = fill material
S (3. letter) = screening leads/foil
I (4. letter) = outer sheath of halogen-free polymer (self-extinguishing)
2 REQUIREMENTS
2.1 Electrical requirements
a) All cables shall have isolated conductors with a rated insulation voltage, UNm of 1 kV.
2.2 Mechanical requirements
a) All conductors shall be constructed of stranded annealed wires of copper or aluminium.
- The conductors may have a circular shape or a sectorial shape.
- The insulation for the conductors shall be made of self-extinguishing material.
- The cable core with the conductors should/may include a fill material to make up the cross section arera (i.e. with a minimum of air gap present).
b) The screen shall be with consentric copper wires and suported by a copper foil to improve the EMC properties of the cable (immunity and radiation).
- The total cross section area of the screen conductors shall be harmonized to the actual cross section area of conductors and shall comply with NEK 400.
c) The outer sheath of the cables shall be made of self-extinguishing material.
- The compound of the outer sheath shall be selected to minimize problems with rodents and UV radiation.
- A rip thread may be included under the outer sheath to assist easy removal of the outer sheath.
2.3 Identification of conductors
a) All conductors shall have insulation material with different colours for unique identification.
- In cables with four conductors, the forth one shall be a neutral conductor with a unique light blue colour.
- The remaining conductors, the phase leads, shall all have a different and distingwishable colour.
2.4 Fire properties
a) The cables shall be free of halogens and fulfil the requirements for Class DCA, s2, d2, a2 in (NS-)EN 13501.
2.5 Cable products
F.number is a unique 9-digit number identifying the specific production variant provided by Bane NOR.
2.5.1 Cables with aluminium conductors
a) The following mechanical requirements apply for cables with aluminium conductors:
Number of conductors |
Designation | F.number | Cross section area conductor/screen mm2 Al / mm2 Cu |
Outer diameter mm |
Min. bending diameter (mm) |
Weight (approx.) (kg/100 m) |
---|---|---|---|---|---|---|
3 | IFSI 1kV 3x25A/10 | to be stated | 25 / 10 | 25 | to be stated | to be stated |
4 | IFSI 1kV 4x25A/10 | to be stated | 25 / 10 | 28 | to be stated | to be stated |
3 | IFSI 1kV 3x50A/16 | to be stated | 50 / 16 | 29 | to be stated | to be stated |
4 | IFSI 1kV 4x50A/16 | to be stated | 50 / 16 | 34 | to be stated | to be stated |
3 | IFSI 1kV 3x95A/29 | to be stated | 95 / 29 | 34 | to be stated | to be stated |
4 | IFSI 1kV 4x95A/29 | to be stated | 95 / 29 | 36 | to be stated | to be stated |
3 | IFSI 1kV 3x150A/41 | to be stated | 150 / 41 | 44 | to be stated | to be stated |
4 | IFSI 1kV 4x150A/41 | to be stated | 150 / 41 | 44 | to be stated | to be stated |
3 | IFSI 1kV 3x240A/72 | to be stated | 240 / 72 | 54 | to be stated | to be stated |
4 | IFSI 1kV 4x240A/72 | to be stated | 240 / 72 | 54 | to be stated | to be stated |
2.5.2 Cables with copper conductors
a) The following mechanical requirements apply for cables with copper conductors:
Number of conductors |
Designation | F.number | Cross section area conductor/screen mm2 Cu / mm2 Cu |
Outer diameter mm |
Min. bending diameter (mm) |
Weight (approx.) (kg/100 m) |
---|---|---|---|---|---|---|
2 | IFSI 1kV 2x1,5/1,5 | to be stated | 1,5 / 1,5 | 11 | to be stated | to be stated |
3 | IFSI 1kV 3x1,5/1,5 | to be stated | 1,5 / 1,5 | 12 | to be stated | to be stated |
4 | IFSI 1kV 4x1,5/1,5 | to be stated | 1,5 / 1,5 | 13 | to be stated | to be stated |
2 | IFSI 1kV 2x2,5/2,5 | to be stated | 2,5 / 2,5 | 12 | to be stated | to be stated |
3 | IFSI 1kV 3x2,5/2,5 | to be stated | 2,5 / 2,5 | 13 | to be stated | to be stated |
4 | IFSI 1kV 4x2,5/2,5 | to be stated | 2,5 / 2,5 | 14 | to be stated | to be stated |
2 | IFSI 1kV 2x4/4 | to be stated | 4 / 4 | 14 | to be stated | to be stated |
3 | IFSI 1kV 3x4/4 | to be stated | 4 / 4 | 15 | to be stated | to be stated |
4 | IFSI 1kV 4x4/4 | to be stated | 4 / 4 | 16 | to be stated | to be stated |
2 | IFSI 1kV 2x6/6 | to be stated | 6 / 6 | 15 | to be stated | to be stated |
3 | IFSI 1kV 3x6/6 | to be stated | 6 / 6 | 16 | to be stated | to be stated |
4 | IFSI 1kV 4x6/6 | to be stated | 6 / 6 | 17 | to be stated | to be stated |
2 | IFSI 1kV 2x10/10 | to be stated | 10 / 10 | 19 | to be stated | to be stated |
3 | IFSI 1kV 3x10/10 | to be stated | 10 / 10 | 20 | to be stated | to be stated |
4 | IFSI 1kV 4x10/10 | to be stated | 10 / 10 | 22 | to be stated | to be stated |
2 | IFSI 1kV 2x16/16 | to be stated | 16 / 16 | 20 | to be stated | to be stated |
3 | IFSI 1kV 3x16/10 | to be stated | 16 / 16 | 21 | to be stated | to be stated |
4 | IFSI 1kV 4x16/10 | to be stated | 16 / 16 | 23 | to be stated | to be stated |
3 | IFSI 1kV 3x25/10 | to be stated | 25 / 16 | 28 | to be stated | to be stated |
4 | IFSI 1kV 4x25/10 | to be stated | 25 / 16 | 30 | to be stated | to be stated |
3 | IFSI 1kV 3x35/16 | to be stated | 35 / 16 | 26 | to be stated | to be stated |
4 | IFSI 1kV 4x35/16 | to be stated | 35 / 16 | 28 | to be stated | to be stated |
3 | IFSI 1kV 3x50/25 | to be stated | 50 / 25 | 29 | to be stated | to be stated |
4 | IFSI 1kV 4x50/25 | to be stated | 50 / 25 | 31 | to be stated | to be stated |
3 | IFSI 1kV 3x70/35 | to be stated | 70 / 35 | 33 | to be stated | to be stated |
4 | IFSI 1kV 4x70/35 | to be stated | 70 / 35 | 36 | to be stated | to be stated |
3 | IFSI 1kV 3x95/50 | to be stated | 95 / 50 | 37 | to be stated | to be stated |
4 | IFSI 1kV 4x95/50 | to be stated | 95 / 50 | 40 | to be stated | to be stated |
3 | IFSI 1kV 3x120/70 | to be stated | 120 / 70 | 40 | to be stated | to be stated |
4 | IFSI 1kV 4x120/70 | to be stated | 120 / 70 | 44 | to be stated | to be stated |
3 | IFSI 1kV 3x150/70 | to be stated | 150 / 70 | 44 | to be stated | to be stated |
4 | IFSI 1kV 4x150/70 | to be stated | 150 / 70 | 50 | to be stated | to be stated |
3 | IFSI 1kV 3x185/95 | to be stated | 185 / 95 | 48 | to be stated | to be stated |
4 | IFSI 1kV 4x185/95 | to be stated | 185 / 95 | 54 | to be stated | to be stated |
3 | IFSI 1kV 3x240/120 | to be stated | 240 / 120 | 55 | to be stated | to be stated |
4 | IFSI 1kV 4x240/120 | to be stated | 240 / 120 | 60 | to be stated | to be stated |
2.6 Markings
a) The outer sheath of the cable shall have easy readable and durable markings with the following information:
- manufacturer's name
- designation
- F.number
- accumulative length at every meter of the actual production length (Note)
- preferably also a unique production identity
- fire clasification according to (NS-)EN 13501
- year of production
- € marking
(Note) The first and the last length figures shall be readable at/on the production package (drum or other package).
2.7 Quality certificate
a) A quality certificate containing test results or control check points shall accompanying the cable and the invoice. The quality certificate shall indicate the purchase number.
2.8 Documentation, language
a) Product sheets shall be available in Norwegian.
3 ENVIRONMENTAL CONCERNS
a) All cables shall be fitted with protective caps at both ends to avoid intrusion of moisture and contamination.
b) Production, use and disposal of the products shall be possible obeying national regulations (Forurensningsloven).
4 REFERENCES
Undated references are supposed to be the last updated version, including any amendments and updates.
- NEK 400: Elektriske lavspenningsinstallasjoner / Electrical low voltage installations (http://www.standard.no/nettbutikk/ - www.nek.no)
- EN 13501: Fire classification of construction products and building elements – Part 1: Classification using data from reaction to fire tests
5 CONFORMANCE LIST
Clause | req. | Complient: (YES / NO ) |
... any comments |
---|---|---|---|
2. | ---/--- | REQUIREMENTS | |
2.1 | ---/--- | Electrical requirements | |
a | |||
2.2 | ---/--- | Mechanical requirements | |
a | |||
b | |||
c | |||
2.3 | ---/--- | Identification of conductors | |
a | |||
2.4 | ---/--- | Fire properties | |
a | |||
2.5 | ---/--- | Cable types | |
2.5.1 | ---/--- | Cables with copper conductors | |
a | |||
2.5.2 | ---/--- | Cables with aluminium conductors | |
a | |||
2.6 | ---/--- | Markings | |
a | |||
2.7 | ---/--- | Quality certificate | |
a | |||
2.8 | ---/--- | Documentation, language | |
a | |||
3. | ---/--- | ENVIRONMENTAL CONCERNS | |
a | |||
b |